Heating Menu / 1.2 - Control temperature by

Menu 1.2
Menu 1.2 - Temperature Regulation Based On

This section of the menu is used to set the parameters for heating regulation.

– when this option is selected, MiniHPC will regulate the output of the outdoor unit to maintain the room temperature at the set value. This is similar to temperature regulation in a conventional air conditioner. However, to prevent a high increase in the temperature of the heating water, the system also monitors the maximum temperature of the heating water next to the item .

– The regulation of the output is carried out in such a way that a constant temperature of the heating water is maintained, which is set next to this item. This option is the default.

– The output regulation is carried out so that the temperature of the heating water is maintained according to the settings of the equithermal curve in the 1.3 Equithermal regulation, while the temperature set next to the item acts as the maximum limit for the heating water temperature for the equithermal regulation curve.

– The regulation of the heating water temperature can be controlled either according to the inlet water temperature T2 into the heat exchanger, or the outlet water temperature T3. The inlet temperature T2 is more stable with higher inertia, so any change in the output of the outdoor unit is reflected on this temperature with a higher delay. Therefore, this value is chosen as the default. When regulating according to T3, it often happens that the output of the outdoor unit cycles excessively in order to maintain the set outlet temperature, because any change in the output is reflected in the outlet water temperature within a few minutes.