Cooling Menu / 2.1 - Turn on/off cooling by

Menu 2.1
Menu 2.1 - Enable Cooling Based On

This section of the menu sets the conditions for initiating cooling.

– when this option is selected (which is the default), cooling will start as soon as cooling is activated on the main menu page (activated button with a snowflake).

– cooling will be activated only if the on/off thermostat, which is connected by cable to the terminals S2, is switched on.

– similar to the previous case, cooling will be activated by the signal from the on/off thermostat, but in this case the logic is inverted. When the thermostat is turned off, cooling will be activated. This is useful in cases where one thermostat is used for both heating and cooling.

– if this option is selected, cooling will be activated/deactivated according to the setting of in the menu 2.2 Control temperature by with the configured hysteresis, which will be displayed after choosing this option.
Example: The room temperature T1 is set to 25°C and the hysteresis is 0.5°C. Cooling will be activated if the room temperature rises above 25°C and will be deactivated if it drops below 24.5°C.

Menu 2.1 - T1 Thermostat
Menu 2.1 - Choosing T1 as Thermostat