Logs Menu

In this section of the device, error codes that occurred over time are recorded. The time of the error event and the error code are displayed.

Code Error Description/Cause
T1 Temperature T1 Faulty/disconnected NTC sensor T1
T2 Temperature T2 Faulty/disconnected NTC sensor T2
T3 Temperature T3 Faulty/disconnected NTC sensor T3
T4 Temperature T4 Faulty/disconnected NTC sensor T4
T5 Temperature T5 Faulty/disconnected NTC sensor T5
T6 Temperature T6 Faulty/disconnected NTC sensor T6
FS Flow Switch S1 Flow error at input S1
FI Flow Sensor I1 Flow error at input I1. No or low flow below the value set in menu 8.1 Flow protection
E6 Communication Error Disconnected, damaged, or incompatible outdoor unit
FP Frost Protection Temperature T3 at the heat exchanger outlet lower than the set frost protection temperature in menu 8.2 Frost protection
F3 ODU - F3 Outdoor unit temperature sensor error – outdoor temperature
F4 ODU - F4 Outdoor unit temperature sensor error – evaporator temperature