DHW Menu / 3.8 - DHW circulation pump

Menu 3.8
Menu 3.8 - DHW circulation pump

The circulation pump for DHW can be controlled by a simple plug-in timer or left to be triggered by MiniHPC.
To control the pump, you can adjust 2 time intervals (e.g. morning and evening), adjust cycle switching and pause times between pump activations, and a function for sterilizing the circulation circuit is also available. This means that the circulation pump will switch on for a set duration whenever the water heater is heated to a high temperature by function 3.3 Anti-legionella. This ensures flushing the piping with hot water.

In the menu section 2 time parameters are adjustable. The first sets the number of minutes the circulation pump will remain inactive after the water heater reaches high temperature (so the water heater can also be sterilized without being immediately cooled down by circulation). The second parameter sets the number of minutes the pump will circulate hot water in the circulation circuit.

To activate this function, it is necessary to assign the DCP function to the selected Relay output in menu 5.2 Relay remap.
A quick shortcut to the relay remapping menu is available by pressing the button at the top of this menu.